)$ꢀꢁꢂ&ꢃꢄꢃ)$ꢀꢁꢂ&ꢅ&1
)$ꢀꢆꢂ&3ꢃꢄꢃ)$ꢀꢆꢂ&3ꢅ&1
3URJUDPPLQJꢀ*XLGHꢀ
DY
REA
ED
M
AR
R
3
6
9
#
2
5
8
0
1
4
7
A
B
C
D
A260
F
AR
M
ED
READ
Y
OFF
ON
R
AWA
Y
1
4
7
2
5
8
0
3
6
9
#
ST
A
Y
P
A
G
E
F
A560
R
K5305-5PR 7/01
352*5$00,1*ꢀ)250
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Entries shown in dashed boxes indicate partition entries for FA168C only (not applicable for FA148CP).
Field Function
SYSTEM SETUP ( 20– 29)
Data Entries
Programmable Values
✱
✱
4 digits, 0–9
✱
20 INSTALLER CODE
|
|
|
[4112]
[0,0]
0 = no; 1 = yes
✱
21 QUICK ARM ENABLE
Part. 1 Part.2
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
✱
22 RF JAM OPTION
[0]
✱
0 = none UL: must be “0”
1 = bypass open zones
23 FORCED BYPASS
[0,0]
Part. 1 Part. 2
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
✱
24 RF HOUSE ID CODE
|
|
|
Part. 1 Part. 2 Common
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
✱
26 CHIME BY ZONE
[0]
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
✱
27
X–10 HOUSE CODE
[0]
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for " ", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
✱
28 ACCESS CODE FOR
|
[00]
✱
4285/4286 PHONE MODULE
(Partition 1 only)
✱
0 = disable; 1 = enable
29 LONG RANGE RADIO OUTPUT
[0]
✱
✱
ZONE SOUNDS AND TIMING ( 31 – 39)
✱
31 ONE AUDIBLE ALARM PER ZONE
0 = no UL: must be “0”; 1 = yes
[0]
[0]
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be “1” for fire install.
✱
32 FIRE ALARMSOUNDER TIMEOUT
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min;
4 = 16 min; UL: minimum “1” (4 min.)
✱
33 ALARM SOUNDER TIMEOUT
[1]
00–99 = seconds of exit delay time for each partition
Common zones use same delay as partition 1.
✱
34 EXIT DELAY
|
|
[70,70]
[30,30]
Part. 1 Part. 2
00–99 = seconds of entry delay #1 time for each
partition; UL: 45 seconds max.
Common zones use same delay as partition 1.
✱
35 ENTRY DELAY #1 (zone type 01)
|
|
Part. 1 Part. 2
00–99 = entry delay #2 time for each partition;
UL: 60 seconds max.
Common zones use same delay as partition 1.
✱
36 ENTRY DELAY #2 (zone type 02)
|
|
[60,60]
Part. 1 Part. 2
0 = no; 1 = yes
✱
37 AUDIBLE EXIT WARNING
[1,1]
Part. 1 Part. 2
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
✱
38 CONFIRMATION OF ARMING DING
[0,0]
Part. 1 Part. 2
✱
39 POWER UP IN PREVIOUS STATE
0 = no; 1 = yes UL: must be “1”
[1]
✱
✱
DIALER PROGRAMMING ( 40 – 42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for ' '; #+12 for '#'; #+13 for a 2-second pause. If fewer than the
✱
✱
maximum digits entered, exit the field by pressing [ ] and next desired field number.
✱
40 PABX ACCESS CODE
|
|
|
|
|
Enter up to 6 digits. To clear entries from field, press ✱40✱ .
✱
✱
41 PRIMARY PHONE No.
42 SECOND PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
.
|
|
|
|
|
|
✱
✱
Enter up to 20 digits. To clear entries, press 41
|
|
|
|
|
|
|
|
|
|
|
|
|
.
|
|
|
|
|
|
✱
✱
Enter up to 20 digits. To clear entries, press 42
– 3 –
NOTE: Entry of a number other than one specified will give unpredictable results.
✱
For fields *43-*46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; #+15 for F. Enter [ ] as the fourth digit if a 3-digit account number (for 3+1 dialer
✱
reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing (and press next field number) if only 3
digits are used. E.g., For Acct. B234, enter: #+11| 2 | 3 | 4
See box above for entries. To clear entries
*.
✱
✱
✱
✱
43 PARTITION 1 PRIMARY SUBS. ACCT. No.
44 PARTITION 1 SECONDARY SUBS. ACCT. No.
45 PARTITION 2 PRIMARY SUBS. ACCT. No.
46 PARTITION 2 SECONDARY SUBS. ACCT. No.
|
|
|
|
|
|
[FFFF]
[FFFF]
*
from field, press 43
See box above for entries. To clear entries
*
*
from field, press 44 .
See box above for entries. To clear entries
|
|
|
|
[FFFF]
[FFFF]
*
*
from field, press 45 .
See box above for entries. To clear entries
|
|
*
*
from field, press 46 .
If Cent. Sta. IS NOT on a WATS line:
0=Pulse Dial; 1=Tone Dial;
✱
47 PHONE SYSTEM SELECT
[1]
if Cent. Sta. IS on a WATS line:
2 = Pulse Dial ; 3 = Tone Dial
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
✱
48 REPORT FORMAT
[70]
primary secondary
6 = 4+2 ADEMCO EXPRESS
7 = ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
0 = Disable (Backup report only)
✱
49 SPLIT/DUAL REPORTING
[0]
Primary Phone No.
Phone No.
1 = Alarms, Restore, Cancel
Second
Others
2 = All except Open/Close, Test Open/Close,
Test
3 = Alarms, Restore, Cancel
All
4 = All except Open/Close, Test All
5 = All
All
✱
50 15 SEC DIALER DELAY (BURG)
0 = no UL: must be “0”; 1 = yes
[0]
[0]
0 = Radionics (0-9, B-F)
1 = SESCOA (0-9 only reporting)
Select “0” for all other formats.
✱
53 SESCOA/RADIONICS SELECT
Delay selectable from 0 to 225 secs in 15-sec
increments.
✱
54 DYNAMIC SIGNALING DELAY
[0]
0 = no delay (both signals sent), 1 = 15 secs,
2 = 30 secs, etc. UL: must be “0”
0 = Primary Dialer first; 1 = Long Range Radio
first.
✱
55 DYNAMIC SIGNALING PRIORITY
[0]
✱
✱
✱
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES ( 59 – 76, & 89):
For 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (not #+10) in the first box will disable a report. A 0 (not #+10) in the second box will result in automatic advance to the next field.
For Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
A 0 (not #+10) in the second box will eliminate the expanded message for that report. A 0 (not #+10) in both boxes will disable the report.
For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the first box, to enable zone to report (entries in the second boxes are ignored).
A 0 (not #+10) in the first box disables the report. UL: see installation instructions for requirements
✱
✱
SYSTEM STATUS REPORT CODES ( 59– 68)
✱
59 EXIT ERROR REPORT CODE
[0]
See box above.
✱
60 TROUBLE REPORT CODE
|
|
|
|
|
[00]
[00]
[00]
[00]
[00]
See box above.
✱
61 BYPASS REPORT CODE
See box above.
✱
62 AC LOSS REPORT CODE
See box above.
✱
63 LOW BAT REPORT CODE
See box above.
✱
64 TEST REPORT CODE
See box above. Use Scheduling mode to set periodic test reports.
✱
65 OPEN REPORT CODE
[0,0,0]
See box above.
Part. 1 Part. 2 Common
✱
66 ARM AWAY/STAY RPT CODE
See box above.
[0,0,0,0,0,0]
Away Stay
Part. 1
Away Stay
Part. 2
Away Stay
Common
– 4 –
✱
67 RF XMTR LOW BAT REPORT CODE
|
|
[00]
[00]
See box on previous page.
UL: must be enabled if wireless devices are used
See box on previous page.
✱
68 CANCEL REPORT CODE
✱
✱
RESTORE REPORT CODES ( 70 – 76)
✱
70 ALARM RESTORE RPT CODE
[0]
See box on previous page.
See box on previous page.
See box on previous page.
See box on previous page.
See box on previous page.
✱
71 TROUBLE RESTORE RPT CODE
|
|
|
|
|
[00]
[00]
[00]
[00]
[00]
✱
72 BYPASS RESTORE RPT CODE
✱
73 AC RESTORE RPT CODE
✱
74 LOW BAT RESTORE RPT CODE
✱
75 RF XMTR LO BAT RST RPT CODE
See box on previous page.
UL: must be enabled if wireless devices are used
See box on previous page.
✱
76 TEST RESTORE RPT CODE
|
[00]
✱
✱
OUTPUT AND SYSTEM SETUP ( 77 – 93)
0 = Disabled
✱
✱
77 DAYLIGHT SAVINGS TIME
|
|
[4][10]
[1][5]
1-12 = January-September (1 = Jan, 2 = Feb, etc)
#+10 = October; #+11 = November; #+12 = December
START\END MONTH
0 = disabled, 1 = first, 2 = second, 3 = third
4 = fourth, 5 = last, 6 = next to last, 7 = third to last
78 DAYLIGHT SAVINGS TIME
START\END WEEKEND
0 = no, 1 = partition 1 only
2 = partition 2 only, 3 = both partitions
✱
84 AUTO STAY ARM
[0]
[0]
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
✱
85 CROSS ZONE TIMER
1 = 30 seconds 7 = 3 min
2 = 45 seconds 8 = 4 min
3 = 60 seconds 9 = 5 min
4 = 90 seconds #+10 = 6 min
#+13 = 10 min
#+14 = 12 min
#+15 = 15 min
This option not for use in UL installations.
5 = 2 minutes
#+11 = 7 min
(assign cross zones on zone list 4, with *81 Menu mode)
0 = no, 1 = yes
✱
86 CANCEL VERIFY
[0]
[0]
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
✱
87 MISC. FAULT DELAY TIME
1 = 30 seconds 7 = 3 min
2 = 45 seconds 8 = 4 min
3 = 60 seconds 9 = 5 min
4 = 90 seconds #+10 = 6 min
#+13 = 10 min
#+14 = 12 min
#+15 = 15 min
(used with Configurable Zone Types “digit 6”)
5 = 2 minutes
#+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm
zones when used in fire and/or UL burglar alarm installation
See box on previous page for report code entries.
✱
89 EVENT LOG FULL REPORT CODE
|
[00]
0 = None; 1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore;
✱
90 EVENT LOG ENABLES
[3]
4 = Bypass/Bypass Restore;
NOTE: System messages are
logged when any non-zero
selection is made.
8 = Open/Close. Example: To select “Alarm/Alarm
Restore”, and “Open/Close”, enter 9 (1 + 8); To select
all, enter #15.
0 = None
1 = Local Lockout
2 = Sounder Delay
✱
91 OPTION SELECTION
[8]
4 = AAV UL: do not use AAV
8 = Exit Delay Restart
E.g. (multiple choice): for AAV (4) plus Exit Delay restart
(8) enter # + 12; for all (1 + 2 + 4 + 8), enter # + 15.
✱
Digit 1:: 0 = disabled, 1-15 = 1 min - 15 min
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min;
#+13 = 13 min; #+14 = 14 min; #+15 = 15 min)
Digit 2:
92 PHONE LINE MONITOR ENABLE
[0,0]
UL: see Inst. Instructions for requirements
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output device
STARTS. If either partition is armed, external sounder
activates also. NOTE: Output Device must either be
programmed to be STOPPED in field ✱80 or
STOPPED by Code + # + 8 + output number.
0 = Unlimited Reports; 1 = 1 report; 2 = 2 reports
UL: must be “0”
✱
93 No. OF REPORTS IN ARMED PERIOD
[0]
PER ZONE (Swinger Suppression)
– 5 –
✱
✱
DOWNLOAD INFORMATION ( 94, 95)
✱
94 DOWNLOAD PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
✱
Enter up to 20 digits, 0–9; #+11 for ' '; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused
✱
spaces. If fewer than 20 digits, exit field by pressing (and press 95, if entering next field). To clear
✱
✱
entries from field, press 94 . UL: downloading may be performed only if a technician is at the site.
0 = Disable Station Initiated Download;
1–14 = number of rings (1–9, # +10 =10, # +11 =11,
# +12 =12, # +13 =13, # +14 =14);
✱
95 RING COUNT FOR DOWNLOADING
[15]
15 = answering machine defeat (# +15 =15).
NOTE: Do not enter “0” if using 4285/4286 Phone Module.
PAGER OPTIONS (*160-*172)
✱
160 PAGER 1 PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
✱
Enter up to 20 digits. 0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
✱
161 PAGER 1 CHARACTERS
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
✱
0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
For each partition, select from the following options:
0 = no reports sent
1 = Open/closes all users
✱
162 PAGER 1 REPORTING OPTIONS
Part. 1 Part. 2 common
[0,0,0]
4 = All alarms and troubles
5 = All alarms / troubles, and open/closes for all users
12 =Alarms / troubles for zones entered in zone list 9
13 =Alarms / troubles for zones entered in zone list 9,
and open\closes for all users
✱
163 PAGER 2 PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
✱
Enter up to 20 digits. 0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
✱
164 PAGER 2 CHARACTERS
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
✱
0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
See field *162 for reporting options. Select for each
partition (use zone list 10 if using options 12 or 13).
✱
165 PAGER 2 REPORTING OPTIONS
[0,0,0]
Part. 1 Part. 2 common
✱
166 PAGER 3 PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
✱
Enter up to 20 digits. 0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
✱
167 PAGER 3 CHARACTERS
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
✱
0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
See field *162 for reporting options. Select for each
partition (use zone list 11 if using options 12 or 13).
✱
0,0,0]
168 PAGER 3 REPORTING OPTIONS
Part. 1 Part. 2 common
✱
169 PAGER 4 PHONE No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
✱
Enter up to 20 digits. 0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
✱
170 PAGER 4 CHARACTERS
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
✱
0–9; #+11 = ' '; #+12 = '#'; #+13 = 2-second pause.
See field *162 for reporting options. Select for each
partition (use zone list 12 if using options 12 or 13).
✱
[0,0,0]
Part. 1 Part. 2 common
171 PAGER 4 REPORTING OPTIONS
0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes
This delay is for ALL pagers in the system.
✱
172 PAGER DELAY OPTION FOR ALARMS
[3]
NOTE: The delay does not reset for new alarms
occurring while an existing pager delay is in progress.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
0 = disable; 1 = Clean Me signal reports;
Note: If Clean Me is enabled, you must enter “3” in
field ✱56 programming for zone 1 response time.
✱
174 CLEAN ME REPORTING OPTIONS
(for ESL smoke detectors)
[0]
0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
✱
177 DEVICE DURATION 1, 2
[0] [0]
1 = 30 seconds 7 = 3 min
2 = 45 seconds 8 = 4 min
3 = 60 seconds 9 = 5 min
#+12 = 8 min
#+13 = 10 min
#+14 = 12 min
(used in *80 Menu mode-Device Actions 5/6)
1
2
4 = 90 seconds #+10 = 6 min #+15 = 15 min
5 = 2 minutes
0 = 60 Hz; 1 = 50 Hz
✱
181 50/60 HERTZ AC OPERATION
[0]
– 6 –
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
✱
182 CONFIGURABLE ZONE TYPE 90
1
2
3
4
5
6
7
8
9
10
Enter the appropriate value for each entry, 1-10, based on the charts provided on
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
Enter the desired 3-digit Contact ID® report codes for
90 ALARM ID: XXX
✱
183 ZONE TYPE 90 REPORT CODES
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [ ]
moves forward. Press [ ] when done to continue.
TROUBLE ID: XXX
IMPORTANT: Use existing Contact ID®
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
✱
184 CONFIGURABLE ZONE TYPE 91
1
2
3
4
5
6
7
8
9
10
Enter the appropriate value for each entry, 1-10, based on the charts provided on
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
Enter the desired 3-digit Contact ID® report codes for
91 ALARM ID: XXX
✱
185 ZONE TYPE 91 REPORT CODES
IMPORTANT: Use existing Contact ID®
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [ ]
moves forward. Press [ ] when done to continue.
TROUBLE ID: XXX
NOTE: Options for keypad address 16 are set by the factory and cannot be changed.)
KEYPAD OPTIONS (*190-*196
NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give
unpredictable results.
Partition: 0 = keypad disabled; 1-3 = part. no. (3 = com)
✱
190 KEYPAD 2 ADDRESS 17
[0] [0]
Sound
Sound:
0 = no suppression
Partition/
Enable
1 = suppress arm/disarm and E/E beeps
2 = Suppress chime beeps only
3 = suppress arm/disarm, E/E, and chime
beeps
FA168C: enter partition
FA148CP: 1 = enable
0 = disable
✱
✱
✱
✱
✱
✱
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
191 KEYPAD 3 ADDRESS 18
192 KEYPAD 4 ADDRESS 19
193 KEYPAD 5 ADDRESS 20
194 KEYPAD 6 ADDRESS 21
195 KEYPAD 7 ADDRESS 22
196 KEYPAD 8 ADDRESS 23
197 EXIT TIME DISPLAY INTERVAL
[0] [0]
Part./Enable† Sound
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
[0] [0]
Part. /Enable† Sound
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
[0] [0]
Part. /Enable† Sound
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
[0] [0]
Part. /Enable† Sound
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
[0] [0]
Part. /Enable† Sound
See field 190 for entries.
† FA168C: enter partition
FA148CP: 1 = enable; 0 = disable
[0] [0]
Part. /Enable† Sound
0 = no display; 1-5 = seconds between display refresh
✱
✱
[0]
[0]
0 = no; 1 = yes (partition no. appears on Alpha Display)
198 DISPLAY PARTITION NUMBER
(for Alpha Display Keypads)
0 = 3-digit display (“1” + device address)
1 = 2-digit fixed-display as “91”
✱
199 ECP FAIL DISPLAY
[0]
– 7 –
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185. Configurable zone types 92 and 93 (FA168C only) can only be programmed using the downloader
software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
Entries for Fields *182 and *184
ENTRY 1 (see note 5 for RF zones) ENTRY 2 (see note 5 for RF zones)
Entry Zone Type 90
(field *182)
1
2
3
4
Zone Type 91
(field *184)
Response when system disarmed and zone is:
Auto
Restore
Vent Zone
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = no
4 = yes
0 = no
8 = yes
5
6
Entry 1 = EOL + Open
Entry 2 = Short + auto restore + vent zone
ENTRY 3 (see note 5 for RF zones) ENTRY 4 (see note 5 for RF zones)
7
8
9
10
Response when armed STAY and zone is:
Byp. when
disarmed
Byp. when
armed
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = no
4 = yes
0 = no
8 = yes
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
Entry 3 = EOL + Open
ENTRY 5 (see note 5 for RF zones) ENTRY 6(see note 5 for RF zones)
Response when armed AWAY and zone is: Dial Delay
Entry 4 = Short + byp. disarmed + byp. armed
Fault Delay
(see field *50) (see field *87)
Intact EOL
Open
RF zone N/A
Shorted
RF zn off-normal
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = no
4 = use delay
0 = no
8 = use delay
see note 1
Entry 5 = EOL + Open
Entry 6 = Short + dial delay + fault delay
INTACT
EOL
OPEN
SHORTED
ENTRY 7
ENTRY 8
ZONE-003-V0
Zone Conditions Represented
in Entries 1-6
Display Faults
Power Reset/
Verification
Use Entry
Delay 1/2
Use Exit
Delay
Respond as
Interior Type
0 = show alarms 0 = no
0 = no
1 = delay 1
2 = delay 2
0 = no
4 = use exit
delay
0 = no
8 = yes
NOTES:
when armed 4 = power reset
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
& disarmed
1 = don’t show
alarms when
after fault
(by code + OFF)
12 = verification
(see zone
see note 2
unpredictable results may occur.
armed (show
alarms, trbles,
faults when
2. To create an interior type zone, select
“respond as interior zone type” (Entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
type 16)
disarmed)
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [ ] key is pressed.
ENTRY 9
ENTRY 10
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
Alarm Sounds
Use Bell
Timeout
Respond as
Fire Zone
0 = no
Trouble
Sounds
0 = none
Chime when
Chime Mode On
0 = no
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for off-
normal RF zone conditions.
0 = none
1 = steady
keypad
0 = no
4 = yes
8 = yes
1 = periodic
beep
4 = yes
2 = steady bell see fields *32,
and keypad *33
3 = pulsing bell
see zone type
09; see note 4
2 = trouble
beeps
6. Zone-Doubling/Double-Balanced: A short
on either zone of a zone-doubled pair or
on a double-balanced zone causes a
tamper condition.
and keypad
Entry 9 = alarm sounds + bell timeout + fire zone
Entry 10 = trouble sounds + chime
– 8 –
*56 ZONE PROGRAMMING WORKSHEET (FA148CP supports up to 32 zones: 1-6, 9-34) [default shown in brackets]
Zone Zn
Type Part.Report
Input
Type Loop Rsp. Time Serial
No.
Location
[09]
[01]
[03]
[03]
[03]
[03]
[03]
[03]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[HW]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
1
2
3
4
5
6
7
8
[HW]
[HW]
[HW]
[HW]
[HW]
[HW]
[HW]
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
95
96
99
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
[BR]
N/A
Reserved Zones
91 = addressable
device report
enable/disable
default zone
type = [05].
92 = Duress report
enable/disable
[00]
[00]
[06]
N/A N/A
N/A N/A
N/A N/A
N/A
N/A
N/A
keypad [1] / [ ]
keypad [3] / [#]
keypad [ ] / [#]
N/A
N/A
NOTES: Zone Type: see chart on page 12; Input Type: HW (1-zones 1-8), AW (2-zones 9-48), RF (3-zones 9-48), UR (4-zones 9-48), BR (5-zones 49-
64); Response Time: 0 (10msec), 1 (350msec), 2 (700msec), 3 (1.2 sec)
– 9 –
*57 FUNCTION KEY PROGRAMMING
Option Function
A
B
C
D
Comments
01
02
03
04
05
06
07
08
09
10
11
12
00
Paging
Time Display
Arm AWAY
Arm STAY
Arm NIGHT-STAY
Step Arming
Device Activation
Comm. Test
Macro Key 1
Macro Key 2
Macro Key 3
Macro Key 4
Emergency Keys:
Personal Emergency
Silent Alarm
Audible Alarm
Fire
Device:
Emergency Keys: A = [1] / [ ]
B = [ ] / [#]
C = [3] / [#]
79,
OUTPUT RELAYS/POWERLINE CARRIER DEVICES WORKSHEET FOR
80 and 81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
79 RELAY/POWERLINE CARRIER DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE
OUTPUT TYPE (09-16 apply to FA168C only)
Relay
Output Module Pos
X10
Unit
No.
Relay
Output Module Pos
X10
Unit
No.
(1-4)
Description
(1-4)
Description
No.
01
02
03
04
05
06
07
08
Addr.
No.
09
10
11
12
13
14
15
16
17
18
Addr.
On-Board Trigger 1
On-Board Trigger 2
✱
81
ZONE LISTS FOR OUTPUT DEVICES
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
Note: Record desired zone numbers below, noting that a list may include any or all of system's zone numbers.
List No.Used For…
Contains These Zones…
01
02
03
04
05
06
07
08
09
10
11
12
General Purpose (GP)
General Purpose
Chime-by-Zone or GP
Cross Zones
Night-Stay Zones or GP
General Purpose
General Purpose
General Purpose
Zones activating pager 1
Zones activating pager 2
Zones activating pager 3
Zones activating pager 4
– 10 –
✱
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes: 1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
✱
2. For Powerline Carrier devices (plcd), field 27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Output
Function
Number
(V20P=1-48)
(V15P=1-24)
Activation Type and Detail
Partition
Number
Event (for zone list/activated by)
Action
0 = off
1 = close 2 secs
2 = stay closed FA168C: R = relay
Output
Number
Device
Type
Activated by Zone List Zone Type Zone No.
By Zone List
By Zone No.
(P)
0=delete
1=zn list
2=zn type
3=zn no.
(ZL)
1-8 = list
(ZT)
(see table 00=none
below) 01-64
(ZN)
(if using ZT trig)
0 = restore
1 = alarm
2 = fault
0 = restore
1 = alrm/flt/trbl
0 = any
3 = pulse
4 = toggle
1-18
T = trigger
X = X10
1 = partition 1
2 = partition 2
3 = common
5 = duration 1†† FA148CP:
6 = duration 2†† 1-8, 17, 18
3 = trouble
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used
05 = Trouble Day/Alarm Night 10 = Interior w/Delay
24 = Silent Burglary
01 = Entry/Exit#1
02 = Entry/Exit#2
03 = Perimeter
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire
12 = Monitor Zone
77 = Keyswitch
90-93 = Configurable
14 = Carbon Monoxide
16 = Fire w/Verification
23 = No Alarm Response
04 = Interior Follower
Choices for System Operation are:
20 = Arming–Stay
21 = Arming–Away
22 = Disarming (Code + OFF)
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
36 = **At Bell Timeout***
Note: In normal operation mode:
38 = Chime
39 = Any Fire Alarm
40 = Bypassing
41 = **AC Power Failure
42 = **System Battery Low
43 = Communication Failure
52 = Kissoff
54 = Fire Zone Reset
58 = Duress
60 = AAV Trigger
66 = Function key†
67 = Bell Failure
68 = TELCO Line Fault
78 = keyswitch red LED†††
79 = keyswitch green LED†††
Code + # + 7 + NN Key Entry starts Device
Code + # + 8 + NN Key Entry stops Device
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program field *177.
††† Device action not used for these choices.
– 11 –
Zone Type Definitions
Use this zone type if the zone is not used.
Type 00
Zone Not Used
• Assign to zones that are used for primary entry and exit.
Type 01
• Provides entry delay if the control is armed in the Away or Stay modes.
• No entry delay is provided when the panel is armed in the Instant mode.
• Entry delay #1 is programmable from 0 to 99 seconds for each partition.
Entry/Exit Burglary #1
•
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable from 0 to 99 seconds (field 34).
✱
• Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
• Provides a secondary entry delay, in same manner as entry delay #1.
• Entry delay #2 is programmable from 0 to 99 seconds for each partition.
• Exit delay is same as described for Type 01.
Type 02
Entry/Exit Burglary #2
• Assign to all sensors or contacts on exterior doors and windows.
Type 03
• Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, or Instant
modes.
Perimeter Burglary
• Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
• Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Type 04
Interior Follower
Otherwise this zone type gives an instant alarm.
• Active when the panel is armed in the Away mode.
• Bypassed automatically when the panel is armed in the Stay or Instant modes.
• Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc.
• Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
• Provides an instant alarm if faulted when armed in the Away, Stay, or Instant (night) modes.
• During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
Type 05
Trouble by Day/
Alarm by Night
• Usually assigned to a zone containing an emergency button.
• Sends a report to the central station but provides no keypad display or sounding.
Type 06
24-hour Silent Alarm
• Assign to a zone that has an emergency button.
Type 07
• Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
24-hour Audible Alarm
• Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as
water or temperature sensors.
• Sends a report to the central station and provides an alarm sound at the keypad. (No bell output is
provided.)
Type 08
24-hour
Auxiliary Alarm
• Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
• This zone type is always active and cannot be bypassed.
Type 09
Fire
Note: Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire
smoke detectors; any wireless zone can be used as a fire zone.
• Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
mode.
• Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
delay zone was tripped first.
Type 10
Interior w/Delay
• Bypassed when the panel is armed in the Stay or Instant modes.
• Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "ALARM-
24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent to the Central Station. The
system keypad will display a “check” message indicating the appropriate zone. Upon restoral of the zone,
the message, "RESTORE-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station.
• The “check” message will automatically disappear from the keypad. The zone restores dynamically;
therefore a user code + off sequence is not needed to reset the zone.
• Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.
Type 12
Monitor Zone
• Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
• Assigned to any zone with a carbon monoxide detector.
• The bell output will pulse when this zone type is alarmed.
Type 14
Carbon Monoxide
• Always active and cannot be bypassed.
• Provides a fire alarm when zone is shorted, but only after alarm verified.
• System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
within 90 seconds triggers fire alarm.
Type 16
Fire w/Verification
• Provides a trouble response when zone is open.
•
UL: may not be used on zone 1.
• Arms the system in Stay mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
Type 20
Arm-Stay
– 12 –
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
Type 21
Arm-Away
• Disarms the system when the zone is activated.
• User code for button must be assigned.
Type 22
Disarm
• Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
Type 23*
No Alarm Response
Type 24
• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, or Instant, modes.
• A report is sent to the central station.
Silent Burglary
• Assign to zone wired to a keyswitch.
Type 77
Keyswitch
• These zone types can be programmed for various custom responses. See data fields *182-*185.
UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
Types 90-93
Installer Defined
*The system can still be armed when these zone types are in a faulted condition.
Schedules (installer code + [#] + [6] [4]; master code can only access schedules 01-16 for FA168C, 01-04 for FA148CP, and events
00-07 for both controls; FA148CP supports up to 8 schedules, FA168C supports up to 32 schedules )
No.Event
Device
NoG. roup
NoP.artition
Start
Time/
Stop
Days
Time/
Repeat Random
(see list below)
for “01” events:
enter 01-18
for “02” events: for “04-06” events:
enter 1-8
(yes/no)
(yes/no)
Days
enter 1, 2, or 3
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Events: Master/Installer
Installer Only
01 = device on/off
02 = user access
05 = forced AWAY arm
06 = auto disarm
10 = display custom words 8-10
11 = peridoic test report
03 = latch key report
04 = forced STAY arm
07 = display “reminder”
– 13 –
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000 (Word Space)
• 057 DOOR
• 059 DOWN
• 060 DOWNSTAIRS
061 DRAWER
• 062 DRIVEWAY
• 064 DUCT
– L –
• 106 LAUNDRY
• 107 LEFT
108 LEVEL
• 109 LIBRARY
• 110 LIGHT
111 LINE
• 113 LIVING
• 114 LOADING
115 LOCK
– R –
155 RADIO
– V –
209 VALVE
210 VAULT
212 VOLTAGE
– A –
• 001 AIR
• 002 ALARM
004 ALLEY
005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC
010 AUDIO
• 156 REAR
157 RECREATION
159 REFRIGERATION
160 RF
• 161 RIGHT
• 162 ROOM
163 ROOF
– W –
213 WALL
214 WAREHOUSE
• 216 WEST
• 217 WINDOW
• 219 WING
– E –
• 065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
• 069 EQUIPMENT
• 071 EXIT
– S –
164 SAFE
116 LOOP
117 LOW
• 118 LOWER
220 WIRELESS
– B –
• 012 BABY
165 SCREEN
166 SENSOR
• 167 SERVICE
• 168 SHED
169 SHOCK
• 170 SHOP
171 SHORT
• 173 SIDE
174 SKYLIGHT
175 SLIDING
• 176 SMOKE
• 178 SONS
• 179 SOUTH
180 SPRINKLER
• 182 STATION
184 STORE
• 185 STORAGE
186 STORY
190 SUPERVISED
191 SUPERVISION
192 SWIMMING
193 SWITCH
– X –
222 XMITTER
• 013 BACK
• 014 BAR
• 016 BASEMENT
• 017 BATHROOM
• 018 BED
• 019 BEDROOM
020 BELL
• 021 BLOWER
• 022 BOILER
023 BOTTOM
025 BREAK
– M –
• 119 MACHINE
121 MAIDS
072 EXTERIOR
– Y –
223 YARD
– F –
• 073 FACTORY
075 FAMILY
• 076 FATHERS
• 077 FENCE
• 079 FIRE
• 080 FLOOR
081 FLOW
082 FOIL
– Z –
224 ZONE (No.)
• 225 ZONE
122 MAIN
• 123 MASTER
• 125 MEDICAL
126 MEDICINE
128 MONEY
129 MONITOR
• 130 MOTHERS
• 131 MOTION
132 MOTOR
• 226
• 227
0
1
• 228 1ST
• 229
• 230 2ND
• 231
• 232 3RD
• 233
• 234 4TH
• 235
• 236 5TH
• 237
• 238 6TH
• 239
• 240 7TH
• 241
• 242 8TH
• 243
2
• 026 BUILDING
• 083 FOYER
084 FREEZER
• 085 FRONT
3
– C –
– N –
• 134 NORTH
135 NURSERY
028 CABINET
• 029 CALL
030 CAMERA
031 CAR
033 CASH
034 CCTV
035 CEILING
036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED
• 046 COMPUTER
047 CONTACT
4
– G –
• 089 GARAGE
• 090 GAS
091 GATE
• 092 GLASS
093 GUEST
094 GUN
5
– O –
• 136 OFFICE
• 138 OPEN
139 OPENING
• 140 OUTSIDE
142 OVERHEAD
6
7
– T –
194 TAMPER
196 TELCO
197 TELEPHONE
• 199 TEMPERATURE
200 THERMOSTAT
• 201 TOOL
– H –
8
– P –
• 095 HALL
• 096 HEAT
098 HOLDUP
099 HOUSE
100 INFRARED
• 101 INSIDE
102 INTERIOR
103 INTRUSION
143 PAINTING
• 144 PANIC
145 PASSIVE
• 146 PATIO
147 PERIMETER
• 148 PHONE
150 POINT
151 POLICE
152 POOL
• 153 POWER
9
• 244 9TH
245 Custom Word #1
246 Custom Word #2
247 Custom Word #3
248 Custom Word #4
249 Custom Word #5
250 Custom Word #6
251 Custom Word #7
252 Custom Word #8
253 Custom Word #9
254 Custom Word #10
– D –
• 048 DAUGHTERS
049 DELAYED
• 050 DEN
202 TRANSMITTER
– U –
• 205 UP
• 206 UPPER
• 207 UPSTAIRS
• 208 UTILITY
051 DESK
– J –
104 JEWELRY
• 052 DETECTOR
• 053 DINING
054 DISCRIMINATOR
055 DISPLAY
– K –
• 105 KITCHEN
Note: Bulleted (•) words in boldface type are those that are also available for use by the 4285/4286 Phone Module. If
using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide
annunciation of those words.
CHARACTER (ASCII) CHART (For Adding Custom Words)
32 (space)
41
42
43
44
45
46
47
48
49
)
50
51
52
53
54
55
56
57
58
2
3
4
5
6
7
8
9
:
59
60
61
62
63
64
65
66
67
;
68
69
70
71
72
73
74
75
76
D
E
F
G
H
I
J
K
L
77
78
79
80
81
82
83
84
85
86
M
N
O
P
Q
R
S
T
87
88
89
90
W
X
Y
33
34
35
36
37
38
39
40
!
"
*
+
,
–
.
/
0
1
<
=
>
?
@
A
B
C
#
$
%
&
'
Z
U
V
(
– 14 –
5800 Series Transmitter Input Loop Identification
• All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each
of the inputs requires its own programming zone (e.g., a 5804's four inputs require four programming zones).
• Transmitter inputs entered as:
"RF" (Supervised RF) Type send periodic check-in
signals, as well as fault, restore and low battery signals.
The transmitter must remain within the receiver's range.
LOOP 3
LOOP 2
(REED)
LOOP
1
(PRIMARY)
LOOP 2
LOOP 1
LOOP 1
(TERMINALS)
2
(AUX. CENTER)
“UR" (Unsupervised RF) Type send all the signals that
the "RF" Type does, but the control does not supervise
the check-in signals. The transmitter may, therefore, be
carried off-premises.
3
LOOP
1
(AUX. RIGHT)
LOOP 4
YOU MUST
ENROLL THIS
BUTTON
ALTERNATE
POSITION
FOR LOOP2
5816MN
ENROLL AS "RF"
5817
ENROLL AS "RF"
5802MN
ENROLL AS "UR" OR "RF"
5801
ENROLL AS "UR" OR "RF"
"BR" (Unsupervised Button RF) Type only send fault
signals. They do not send restore or check-in signals.
They will indicate a low battery condition when tested or
activated normally. The transmitter may be carried off-
premises.
LOOP
2
LOOP 3
LOOP
2
YOU MUST
ENROLL THIS
BUTTON
(REED)
LOOP 1
(TERMINALS)
(REED)
LOOP 2
LOOP 1
LOOP 4
LOOP 1
(INTERNAL
SHOCK
LOOP 2
LOOP 3
(TERMINALS)
YOU MUST
ENROLL THIS
BUTTON
SENSOR)
LOOP 3
(TERMINALS)
5819
5819S (WHS
&
BRS)
5804
ENROLL
AS "BR"
LOOP 4
ENROLL AS "RF"
ENROLL AS "RF"
LOOP 1
LOOP 3
•
•
•
Note: For information on any transmitter not shown
above, refer to the instructions accompanying that
•
•
•
•
•
•
•
•
•
•
•
&bull |